Product Details

Level Switches - Paddle Wheel

Flui-Tec is proud to introduce its range of high range of products

Product Specifications

Line Size : 15 to 300mm
Input Voltage: 12 to 24 VDC
Connection: Thread/Flange
Output Type: Pulse /4-20mA
Temp: 0-50/70 deg C,
Pressure : 5/20bar Max
Body : P. P/SS
Paddle : Delryn/SS
Protection : IP65

Features

Paddle wheel flow meters belong to the category of insertion type flow meters. The rotating paddle wheel generates a signal in proportion to the velocity of the moving fluid which is read in terms of the flaw rate. Because the pipe's cross-sectional area is known and remains fixed the average velocity is an indication of the flow rate.

MATERIAL OF CONSTRUCTION

Transducer Housing : POLYPROPYLENE
O-rings : NEOPRENE
Shaft : SS316/HASTALLOY C/PVDF
Rotor : NYLON/PVDF
Maximum %solids : 1% of fluid volume, non-abrasive, non-magnetic, (<100 micron in diameter and length>)
Max. Viscosity : 1 Cp(water) upto 5Cp above 1.5m/sec
Output : 1line 16 chr. LCD display/1line LED/2line LED
Register : Rate of flow - m3/hr Total flow-m3
Standard Cable Length : 1.5mtrs power supply cable for field mounted versions and 10 mtrs signal transmission cable for panel mounted versions
Process Connection : PP wafer drilled as per BS10Table E/ANSI B16.5/SS stub/Glue-on PVC saddle
INSTALLATION FITTINGS

All installation fittings are supplied along with the flow sensor. The sensor may be installed in a PP wafer drilled asper BS10 TABLE E OR ANSI B16.5 standards or a Glue-on PVC saddle or a SS stub welded to a MS/SS plate.

ADD-ON FEATURES *

RELAY OUTPUT
  • 230vac, 1a (Resistive load only) max. with 1NO and 1NC contact. 1 or 2 Relay outputs can be given for giving a signal based on flow rate or total flow or both depending upon the requirements.
  • Customer to clearly specify the number of relay outputs required and also whether the cut-off signal is to be based on rate of floe or total flow.
INTERFACING WITH PLC

An open collector pulse output or a 4-20mA signal can be provided for interfacing with a PLC or connecting to Recorders.

DOSING APPLICATION

Programmable pulsed output available

THE DOWNTIME ELIMINATOR WET TAP VALVE ASSEMBLY

You can completely eliminate downtime resulting from flow sensor maintenance, with the simple addition of the Wet Tap Valve assembly. Should a sensor, rotor, or O-ring need to be replaced, the wet tap assembly provides a safe and fast method of removing a specially extended sensor from your pipe without system shut-down.

    

Related Products

Flui-Tec is proud to introduce its range of high range of products

Our Partner

Aenean suscipit eget mi act